2021.07.11
1. [Products] Introducing Azbil’s Switch Model HP7-_ _ _ & Proximity Sensor Model H3C-H_
2. [Application Notes] Required Straight Pipe Length for Control valves
▢ Reliable for any color or material
▢ Super long-distance, and compact
▢ 3 models for different purposes
See more in the below video:
Find out the product catalog here.
▢ 2 outputs, detection in 4 areas
▢ Automatic setting
▢ Visible safety margin
See more in the below video:
Find out the product catalog here.
The following conditions are required when a control valve is installed in order to ensure a good flow.
Conditions for Control Valve Piping
– More than 10D of straight pipe length on the upstream side
– More than 7D of straight pipe length on the downstream side
(D refer to the nominal pipe diameter)
These conditions will insure a steady and repeatable flow rate.
If these conditions are not met, reduced flow rate, abnormal noise, undesirable vibration, and other fluid system problems may occur. This is illustrated in the “Flow capacity―Test procedure” part of IEC 60534-2-3 (1997) as shown below.
Find out more about Azbil Control Valves’ product line up here.
We would like to receive your feedback to improve for our next publish. If you would like to stop receiving this email, please kindly contact us.
©2008-2020 Azbil Vietnam Co., Ltd. All rights reserved.